The pillar's site-conditions checklist applies here in full: filtration, frost, water hammer and chemical compatibility. A classified area adds its own conditions on top.
Certified conditions of use. The Dosatron D8 ATEX manual includes these conditions:
- Do not rub the unit with a dry cloth (an electrostatic precaution).
- For installation in zone 0, check that there is no charging mechanism around the pump.
- Maximum temperature: 40 °C (104 °F).
Treat these as part of the certification, not as general advice. Keep the unit away from hot machinery surfaces and out of direct sun.
Underground and recycled water. Underground spray water is often recycled and carries fine coal or rock dust. Filter at the inlet, and schedule filter cleaning so the work fits the site's permit-to-work system for the zone.
Viscous concentrates. Binders and some wetting agents may need the viscous-additive kit, recommended above 200 or 400 cPs depending on model. Check viscosity at the coldest underground or outdoor temperature.
Frost on surface installations. Surface coal handling at northern sites needs the same frost protection or drain-down as any other dosing point. Any heated enclosure must suit the hazardous area itself.